RoundV21/IssueFu (2021-10-15 13:01:25)

Solution for now:

Save config, edit vemscfg file:

And File/upload config.

That should display lambda, and not AIM (which is not received => indicated by -FU).

We are checking how to set it from VT. (possibly VT ini change).

Thanks for the patience.


Issue with round (manufactured 2021-08) firmware 0.7.51

REPRODUCED ISSUE in lab. On good track now. Thanks for the patience

config.display_mode[0]=80 THIS CONFIG IS WRONG, >=80 (upper nibble >= 8) is for AIM function, but AIM it does NOT receive.

The gauge is happy that the sensor is working and showing correct lambda in VemsTune.

It can show other things in the top row, but AFR or Lambda just shows "-FU" (indicating possibly Display Peak value="peak value" selected instead of "actual value", or target not reached problem, are the wires safe and sound ?).

Can you do Tools/Firmware verify 0.7.51 ? (just in case)

Please investigate and respond to report crvGcr